4 to 16 Zone Slave Semi Addressable/ Networkable Fire Alarm Control Panel



4 to 16 Zone microprocessor based semi addressable fire alarm SLAVE control panel fully networkable wall mounted type fabricated out of 1.2/1.6mm CRCA sheet, dust and vermin proof, powder coated, with power supply and battery charger, battery backup of 2X12 V 7 AH maintenance free battery.

FEATURES:

  • A highly descriptive 20 character, 4 line LCD, Alphanumeric display is provided for all information.
  • 1000 events logs storing events of fire, open, short, reset, local and network silence with ID, date and time stamp.
  • The slave panel has the facility to communicate all the events with master panel on network and vice‐versa.
  • RS485 networkable with other panels for information sharing.
  • Zone wise fire, open, short, isolate and normal LED indication.
  • Important panel settings are protected by password to prevent unauthorized access. User can change the password and even Enable/Disable protection.
  • Each zone in network can be named as per the requirement either using the menu function or using PC interface software.
  • The panel is able to filter its events like fire, open, short, reset and silence.
  • Alarms can be delayed by one minute to fifteen minute period, in steps of one minute. Different delay periods can be selected on an individual zone basis. Pre alarm helps to prevent false alarms in areas prone to smoke/fire generation.
  • The panel has auto programming day/night mode for pre‐alarm.
  • The panel has the one man test (walk test) facility for the system maintenance purpose; each detector is tested by a single Engineer, without need of returning to the panel.
  • The panel has the facility for nomenclature of the panel / site / department itself.

Specification

Model No.   AD1-UL–4 to AD1-UL–16 (4 Zone to 16 Zone)
Description   Semi Addressable Networkable Programmable Fire Alarm Panel
Description   Semi Addressable Networkable Programmable Fire Alarm Panel
Description   Semi Addressable Networkable Programmable Fire Alarm Panel
Trigger Devices   40-50 Per Zone
Sounders   2 No. In Each Zone / 8No. Common
Compatibility   Compatibility
Mounting   Surface or Semi-Flush
Operating Voltage   Surface or Semi-Flush
Wiring   Wiring
Monitoring   Trigger device circuits open and short circuit fault and detector removal via 22uF 35/40 volt EOL capacitor. Sounder Circuits open and short circuit.
Sounder Circuits   ZC8/4/8 - 2 x 24 Vdc 0.50A ZC8/2 - 2 x 24Vdc 0.25A
Switched outputs   Fire and Fault 1 Volt free c/o 1 at 30 Vdc (each)
PC Interface   Serial Communication The AdCom Using PC Software
Active Repeater   4 to 16 Zone repeater output via main panel (Serial Communication - RS 485 -2 core connection)
Passive Repeater   4 to 16 Zone repeater output via main panel aux supply 24V DC (Serial Communication - RS 485 - 4 core connection)
Indicator   Light emitting diodes (LEDs)
Standby Batteries   2 x 12 volt 7Ah sealed lead acid 24hr standby
Temperature Range   -10oC to + 60oC
Humidity Range   10% to 90% RH (non condensing)
Environmental   IP50
Construction   Cold Rolled Coil Sheet (1.2mm / 1.6mm)
Dimensions   276mm (H) x 410mm (W) x 95mm (D) AD1-UL– 4 to 16 (4 Zone to 16 Zone)
Colour   Snow White
Weight   7.392 Kg AD1-UL– 4 to 16 (4 Zone to 16 Zone) Excluding Printer & Batteries